Got Side Settings - Mitsubishi Electric GT14 User Manual

Hide thumbs Also See for GT14:
Table of Contents

Advertisement

35.2.6

GOT side settings

Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: KEYENCE
• Controller Type: KEYENCE KV-700/1000/3000/
5000
• I/F: Interface to be used
• Driver: KEYENCE KV-700/1000
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
 Communication detail settings
OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
35 - 16
35. CONNECTION TO KEYENCE PLC
35.2 Serial Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
Item
Transmission
Speed
Data Bit
3.
Stop Bit
4.
Parity
Retry
Timeout Time
Host Address
Delay Time
Station No.
Selection
POINT
POINT
POINT
(1) Communication interface setting by Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bit)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the PLC to which the GOT is
connected) in the network of the GOT.
(Default: 0)
Set this item to adjust the
transmission timing of the
communication request from the GOT.
(Default: 0ms)
Specify whether to use the station No.
during communication. If [Yes] is
selected, the station No. is fixed to "0."
(Default: No)
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
3 to 30sec
0 to 9
0 to 300ms
Yes or No