RS485 connection diagram 10)
External cable
GT11H-C side
FG(Shield)
Shield
SDA
W/R (A)
SDB
W/BK (A)
RSA
GY/R (A)
RSB
GY/BK (A)
RDA
O/R (A)
RDB
O/BK (A)
CSA
Y/R (A)
CSB
Y/BK (A)
SG
PK/R (A)
* 2
*1
Terminating resistor should be provided for a temperature controller which will be a terminal.
*2
Connect FG grounding to the appropriate part of a cable shield line.
Precautions when preparing a cable
(1) Cable length
(a) The length of the RS-485 cable used for
connecting the temperature controller to the
communication converter
The length of the RS-485 cable must be 1200m or
less.
(b) The length of the RS-485 cable used for
connecting the temperature controller to the GOT
The total distance (between GOT and controllers)
of RS-485 cable must be 13m or less.
(2) Connector conversion box side connector
For the connector conversion box side connector, refer
to the following.
6.6 Connector Conversion Box
(3) External cable side connector
For the connector specifications of the external cable
side, refer to the following.
8.2 External Cable, Relay Cable
(4) YOKOGAWA temperature controller side connector
Use the connector compatible with the YOKOGAWA
temperature controller side.
For details, refer to the user's manual of the
YOKOGAWA temperature controller.
Temperature
controller
TX+
4
TX-
6
RX+
3
RX-
5
SG
2
* 2
Terminating resistor (220Ω 1/4W)
51. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
Temperature
controller
TX+
4
TX-
6
RX+
3
RX-
5
SG
2
* 1
Connecting terminating resistors
(1) YOKOGAWA temperature controller side
When connecting a YOKOGAWA temperature
controller to the GOT, a terminating resistor must be
connected.
51.5 Temperature Controller Side Setting
51.3 Connection Diagram
48
49
50
51
52
53
54
55
51 - 23