38.4 GOT Side Settings

38.4.1
Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: SHARP
• Controller Type: SHARP JW
• I/F: Interface to be used
• Driver: SHARP JW
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

38.4.2 Communication detail settings

OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
38.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Transmission
Speed
3.
Data Bit
4.
Stop Bit
Parity
Click!
Retry
Startup Time
Timeout Time
DelayTime
*1
POINT
POINT
POINT
(1) Communication interface setting by Utility
(2) Precedence in communication settings
38. CONNECTION TO SHARP PLC
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the data length
used for communication with the
connected equipment.
(Default: 7bit)
Specify the stop bit length for
communications.
(Default: 2bit)
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: Even)
Set the number of retries to be performed
when a communication error occurs.
(Default: 0time)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication
to time out.
(Default: 3sec)
Set this item to adjust the transmission
timing of the communication request from
*1
the GOT.
(Default: 0ms)
When connecting to the communication port, set "Delay
Time" of the GOT side to 30ms or more.
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
11. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
38.4 GOT Side Settings
32
33
Range
4800bps,
9600bps,
19200bps
34
7bit (fixed)
2bit (fixed)
Even (fixed)
35
0 to 5times
3 to 30sec
36
3 to 30sec
0 to 300ms
37
38
39
38 - 13