30.4 Precautions

30.4.1 Precautions for use
Occurrence of the same system alarm at different channels
When the advanced system alarm is used, if the system alarms with the same error code occur in different channels
the GOT treats the alarms as the same system alarm.
Therefore, if the system alarms with the same error code occur one by one, the time of later system alarm occurrence
is not reflected to the GOT.
Confirmation of the channel No. at which a system alarm occurred
When a system alarm occurred, confirm the channel No. where the alarm occurred, using the procedure indicated
below.
(1) Check by [System alarm display] of the utility.
15.3 System Alarm Display
(2) Monitor the internal devices of the GOT.
GT Designer3 Version1 Screen Design Manual
30. MULTI-CHANNEL FUNCTION
30.4 Precautions