[Controller Setting] and [Ethernet] of GT
Designer3
(1) Controller setting
Item
GOT NET No.
GOT PLC No.
GOT IP Address
GOT Port No.
(Communication)
GOT Port No.
(Ethernet Download)
Default Gateway
Subnet Mask
Retry
Startup Time
Timeout Time
Delay Time
(2) Ethernet setting
Item
Host
N/W No.
PLC No.
Ethernet
Type
setting No.1
IP Address
Port No.
Communication
POINT
POINT
POINT
[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT Designer3,
refer to the following.
23.3.1 Setting communication interface
(Communication settings)
23 - 32
23. ETHERNET CONNECTION
23.4 PLC Side Setting
Setting (Use default value.)
1
1
192.168.0.18
5001
5014
0.0.0.0
255.255.255.0
3times
3sec
3sec
0ms
Set value
*
1
2
QJ71E71
192.168.3.19
5001 (fixed)
UDP (fixed)
Confirming the communication state of
Ethernet module
(1) When using the Command Prompt of Windows
Execute a Ping command at the Command Prompt of
Windows
.
(a) When normal communication
C:\>Ping 192.168.0.19
Reply from 192.168.0.19: bytes=32 time<1ms
TTL=64
(b) When abnormal communication
C:\>Ping 192.168.0.19
Request timed out.
(2) When abnormal communication
At abnormal communication, check the followings and
execute the Ping command again.
• Mounting condition of Ethernet module
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• IP address of GOT specified by Ping command
POINT
POINT
POINT
Ethernet diagnostics of GX Developer
Ethernet diagnostics of GX Developer is available to a
Ping test from the PLC.
For details of Ethernet diagnostics of GX Developer,
refer to the following manual.
User's manual of the Ethernet module