1.
Click the Connection Destination view
Destination]
[(Connection target data name)] in the
Navigation window of GX Works2.
2.
The [Transfer Setup] is displayed.
3.
Set the [Transfer Setup]:
PC side I/F: Serial USB
PLC side I/F: GOT
Other station: No specification
4.
Double-click [Serial USB] of the PC side I/F to display
[PC side I/F Serial Setting].
5.
Check the following for [PC side I/F Serial Setting].
When connecting the GOT and PC with USB
Mark the [USB] checkbox.
[Connection
6.
Double-click [GOT] of the PLC side I/F to display
[PLC side I/F Detailed Setting of GOT].
7.
Set the [CPU mode] to [LCPU] for [PLC side I/F
Detailed Setting of GOT].
ark the [via GOT (Ethernet) transparent mode]
checkbox and click [Set].
8.
By clicking [Set], the [GOT (Ethernet) transparent
setting] is displayed.
Here, set the built-in Ethernet port QCPU or Ethernet
module, which is firstly connected via a GOT.
9.
Set [NZ2GF-ETB] for [PLC Type].
Set the same number to [IP address] as the number
assigned to NZ2GF-ETB, and click [OK].
In the system configuration example, the setting is as
follows.
[IP address]: 192 168 3 30
31. FA TRANSPARENT FUNCTION
31.6 Personal Computer Side Setting