45.4 GOT Side Settings

45.4.1
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: HITACHI
• Controller Type: HITACHI HIDIC H
• I/F: Interface to be used
• Driver: Set either of the followings.
• HITACHI HIDIC H
• HITACHI HIDIC H (Protocol2)
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

45.4.2 Communication detail settings

OK
Click the
button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
18.1.2 I/F communication setting
45.4.2 Communication detail settings
Make the settings according to the usage environment.
(1) HITACHI HIDIC H
Item
Transmission
Speed
3.
Data Bit
4.
Stop Bit
Parity
Click!
Retry
Timeout Time
Delay Time
Station No.
Selection
45. CONNECTION TO HITACHI IES PLC
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the data length
used for communication with the connected
equipment.
(Default: 7bit)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: Even)
Set the number of retries to be performed
when a communication error occurs.
(Default: 0time)
Set the time period for a communication to
time out.
(Default: 3sec)
Set this item to adjust the transmission
timing of the communication request from
the GOT.
(Default: 0ms)
Specify whether to use the station No.
during communication.
If [Yes] is selected, the station No. is fixed
to "0."
(Default: Yes)
45.4 GOT Side Settings
40
41
Range
4800bps,
9600bps,
19200bps,
38400bps
42
7bit (fixed)
1bit (fixed)
Even (fixed)
43
0 to 5times
3 to 30sec
44
0 to 300 (ms)
Yes or No
45
46
47
45 - 11