52.5 Control Equipment Side Setting

POINT
POINT
POINT
AZBIL control equipment
For details of AZBIL control equipment, refer to the
following manual.
User's Manual of the AZBIL control equipment
Model
DMC10
DMC50
SDC15, SDC25/26, SDC35/36
SDC20/21
SDC30/31
SDC40A/40B/40G
SDC45/46
CMS, CMF015
CML, CMF050
Control
equipment
MQV
MPC
PBC201-VN2
MVF
AUR350C, AUR450C
RX
CMC10B
AHC2001 CPU module
AHC2001 SCU module
Interface
CMC10L
converter

52.5.1 Connecting to DMC10

Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-D10) of the temperature
controller.
Item
*1
9600bps, 19200bps
Transmission speed
*2
CPL
Communication mode
Data bit
8bits
*1
Even, none
Parity bit
Stop bit
2bits
Communication minimum
1ms, 10ms, 100ms, 200ms
response time
*3*4
0 to F
Station address
*1
Adjust the settings with GOT settings.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
52 - 38
52. CONNECTION TO AZBIL CONTROL EQUIPMENT
52.5 Control Equipment Side Setting
Refer to
52.5.1
52.5.6
52.5.3
52.5.4
52.5.4
52.5.2
52.5.7
52.5.8
52.5.9
52.5.10
52.5.11
52.5.12
52.5.13
52.5.14
52.5.15
52.5.16
52.5.17
52.5.18
52.5.5
Set value
Station address setting
Set the station address using the rotary switch for the
station address.
Rotary switch
for the station address
4
8
0
ADR
C
52.5.2 Connecting to SDC40A/40B/
40G
Communication settings
Make the communication settings by operating the key
of the temperature controller.
Item
*1
9600bps
Transmission speed
Data bit
8bits
*1
Even, none
Parity bit
Stop bit
1bit, 2bits
*2*3
0 to 127
Station address
*1
Set the same transmission speed as that of the GOT side.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
52.5.3 Connecting to SDC15,
SDC25/26 or SDC35/36
Communication settings
Make the communication settings by operating the key
or Smart Loader Package (SLP-C35) of the
temperature controller.
Item
*1
9600bps, 19200bps
Transmission speed
*2
CPL
Communication mode
*1
7bits, 8bits
Data bit
*1
Odd, even, none
Parity bit
*1
1bit, 2bits
Stop bit
Communication minimum
1 to 250ms
response time
*3*4
0 to 127
Station address
*1
Set the same transmission speed as that of the GOT side.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
Front of the
temperature
controller body
Set value
Set value