Setup - Safety - Inventory Tab - MCi iControl User Manual

For ac elevators
Table of Contents

Advertisement

iView - Controller View

Setup - Safety - Inventory Tab

The Inventory tab is used to perform the Safety Inventory Learn procedure. This procedure
must be performed when an inventory fault is generated.
Status
The status section provides fault indicators and a list of known safety boards
attached to the iBox.
• Inventory checksum fault indicator: Indicates that the previously learned value of
the inventory checksum does not match the value currently being reported by the safety
processors. The inventory learn procedure must be performed before the car can run.
• Inventory comparison fault indicator: The Safety boards attached to the iBox do not
match the safety board inventory in the safety system. The inventory learn procedure must
be performed before the car can run.
• Set button: This function is primarily for factory use or for use as instructed by MCE.
Learn
These controls are used to perform the safety inventory learn operation. The indica-
tors on the left show the status of the learn operation and the text window provides information
and instructions.
• Learn button: Learning the inventory causes the safety processors to take an inventory
of the boards attached below the ICE-SAF board. When performing the inventory learn
procedure, the car must be placed on Inspection mode. Follow the instructions in the dis-
play window. When the indicators show Ready, click the Learn button.
• Erase button: Causes the values currently stored in the Safety EEPROMS to be erased.
This should be used as a last resort when troubleshooting inventory faults. Afterwards, the
safety inventory, limit switches and safety configuration must be relearned.
9-150 Manual # 42-02-2222