iControl Messages
Table 6.3 iControl Messages
iControl Messages
Safety B Contract Overspeed Fault, SPB COS FAULT
Description: The car has exceeded the Contract Overspeed setting. This fault may be bypassed on the Diag-
nostics > Fault Bypass tab.
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. The fault will automatically clear 5 seconds after the car stops. The car is then allowed to run again.
2. Check the contract overspeed parameter for proper setting. (iView/Safety Config/General)
Safety B DETS Level 2 Speed Fault, SPB DETS L2 SPEED FLT
Description: The car contacted the Down Emergency Terminal Switch while traveling at over 95% of contract
speed. This fault may be bypassed on the Diagnostics > Fault Bypass tab.
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. The fault will automatically clear 5 seconds after the car stops. The car is then allowed to run again.
2. Check for the proper positioning of the DETS switch in the hoistway.
Safety B Fault Bypass Switch Timed Out
Description: Indicates that a fault bypass has timed out. (Bypasses are allowed for 15 minutes with the iBox
Fault/Function Bypass switch in the ON position.) On Inspection mode, this fault is bypassed indefinitely.
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. To clear this fault, place the Fault/Function Bypass switch to the OFF position.
Safety B Inspection Leveling Overspeed Fault, SPB LOS FAULT
Description: The car exceeded the leveling overspeed limit (detected by safety processor B). This fault may
be bypassed on the Diagnostics > Fault Bypass tab.
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. The fault will automatically clear 5 seconds after the car stops. The car is then allowed to move again.
2. Check the leveling overspeed parameter for proper setting (iView/Safety Config/General).
Safety B Inspection Overspeed Fault, SPB IOS FAULT
Description: The car has exceeded the inspection overspeed limit of 150 fpm (detected by safety processor
B).
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
6
Troubleshooting:
1. The fault will automatically clear 5 seconds after the car stops. The car is then allowed to move again.
Safety B SIB Device Fault, SPB SIB DEVICE FAULT
Description: Safety Processor B has a problem writing Safety Ice Bus.
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. Replace iBox. SAF Board damaged. Contact MCE.
Safety B SIB Device Fault Off (See: Safety B SIB Device Fault)
Safety B Safety Bypass Jumper Timed Out
Description: Safety Processor B has detected that the Safety Bypass Jumper has been on for more than 15
minutes.
Car Reaction: The car will not be allowed to restart after the end of the current run.
Troubleshooting:
1. Remove the iBox Safety Bypass Jumper.
2. If more time is needed in the Safety Bypass mode, then reinstall Safety Bypass Jumper and the 15 min-
ute timer will restart.