Flood Operation Shall Override
tion interaction with other operating modes is user selectable. For the mode(s) of operation
selected, where the requirements of Flood operation are not in agreement with those of the
selected mode, the requirements of Flood operation will take precedence.
During Flood operation, cars shall avoid the flood zones. If inside the flood zones, cars shall
proceed to the nearest floor outside the flood zone immediately unless the doors are open, in
which case the timer (if any) must first elapse:
• Firefighters service: Select if flood operation requirements should override In-car fire-
fighter operation requirements.
• In-car CFSS mode 1: Select if flood operation requirements should override In-car CFSS
mode 1 requirements.
• If doors are open, after (timer) sec. If the car is inside the flood zone and doors are
open, this timer must elapse before the car proceeds to the nearest floor outside the
flood zones.
• In-car CFSS mode 2: Select if flood operation requirements should override In-car CFSS
mode 2 requirements.
• If doors are open, after (timer) sec. If the car is inside the flood zone and doors are
open, this timer must elapse before the car proceeds to the nearest floor outside the
flood zones.
• Emergency medical service (EMS): Select if flood operation requirements should override
the requirements of EMS service.
• If doors are open, after (timer) sec. If the car is inside the flood zone and doors are
open, this timer must elapse before the car proceeds to the nearest floor outside the
flood zones.
• Independent Service: Select if flood operation requirements should override Independent
and Service operation requirements.
• Attendant Service: Select if flood operation requirements should override Attendant Ser-
vice operation requirements.
• Independent and Attendant service if doors are open, after (timer) sec. If the car is
inside the flood zone and doors are open, this timer must elapse before the car pro-
ceeds to the nearest floor outside the flood zones.
Substitute recall floor during flood operation
nated for Emergency Power recall and Fire recall:
• Emergency Power recall: Select the recall floor the elevator is to use during emergency
power operation under flood conditions.
• Fire recall floor: Select if flood operation should modify fire recall operation. If so, set the
recall floor to be used if fire recall is activated during flood conditions.
Configuration - Car Operation
Depending upon code requirements, flood opera-
Substitute floors can be desig-
9
9-77