MCi iControl User Manual page 534

For ac elevators
Table of Contents

Advertisement

iView - Controller View
The programmable options for Sabbath operation include:
• Enable Sabbath Operation: Must be checked for Sabbath operation to be activated/deacti-
vated. Otherwise Sabbath operation is disabled.
• Allow hall call service: Check to allow existing hall calls to be served and new hall calls to
be registered while on Sabbath operation.
• Disable arrival lanterns: During Sabbath operation the arrival lanterns shall be dis-
abled (applies only if "Allow hall call service" is checked).
• Allow car call service: Check to allow existing car calls to be served and new car calls to be
registered while on Sabbath operation.
• Finish existing car calls: When Sabbath operation is activated, the car will service all exist-
ing car calls before beginning Sabbath operation.
• Disable car call buttons light: The car call buttons will not illuminate in response to auto-
matically generated Sabbath operation calls. However, they will illuminate to indicate reg-
istration of car calls in response to call button activation.
• Disable position indicators: During Sabbath operation the position and direction indica-
tors shall be disabled (except for CE Electronics displays).
• Disable load weighing functions: During Sabbath operation the elevator's load weighing
functions shall be disabled (except for pre-torquing).
• Sabbath operation recall flo0r: When Sabbath operation is activated, if a recall floor is des-
ignated, the car will first recall to this floor before beginning Sabbath operation service.
• Sabbath operation start floor: When Sabbath operation is activated, after traveling to the
recall floor (if designated), the car will travel to the start floor (if designated) before begin-
ning Sabbath operation service. The start floor options are:
• Bottom (unidirectional) = Start at the bottom floor and travel up, stopping at desig-
nated Sabbath floors until the top designated floor is reached. What happens next is
determined by the Sabbath trip interval timer and Sabbath operation return floor
parameters.
• Top (unidirectional) = start at the top floor and travel down, stopping at designated
Sabbath floors until the bottom designated floor is reached. What happens next is
determined by the Sabbath trip interval timer and Sabbath operation return floor
parameters.
• Current up (bidirectional) = start at the current floor and travel up (unless down pref-
erence exists, in which case travel down), stopping at designated Sabbath floors until
the top/bottom designated floor is reached. Then, if all designated floors have not been
served at least once, reverse direction, stopping at designated floors until the bottom/
top designated floor is reached. What happens next is determined by the Sabbath trip
interval timer and Sabbath operation return floor parameters.
• Current down (bidirectional) = start at the current floor and travel down (unless up
preference exists, in which case travel up), stopping at designated Sabbath floors until
the bottom/top designated floor is reached. Then, if all designated floors have not been
serviced at lease once, reverse direction, stopping at designated floors until the top/
bottom designated floor is reached. What happens next is determined by the Sabbath
trip interval timer and Sabbath operation return floor parameters.
• Sabbath operation return floor: The car shall travel to the return floor (if specified) after it
has finished servicing all of the Sabbath floors (at least once). Select None or any floor.
9-82 Manual # 42-02-2222