Additional Adjustments And Checks - MCi iControl User Manual

For ac elevators
Table of Contents

Advertisement

Additional Adjustments and Checks

1. On the Configuration > Pattern > Common tab, set Pattern scaling to 100%.
2. On the Configuration > Pattern > Modes tab, set Inspection/High Speed to the desired
value (maximum Inspection speed is 150 fpm). Set the Inspection/Low Speed to 25 fpm.
Note
If the Terminal Switches (UNT5/DNT5) have been installed, and you wish to use the reduced
inspection speed option, you may enable it by checking Reduced inspection speed on the Con-
figuration > Pattern > Modes tab. If not, you may enable Reduced Inspection speed after the
Terminal Switches are installed. (Enabling it now, without switches, would cause the car to run
at 25 fpm.)
3. Stop the car so that the car top can be accessed from the top hall door.
Note
NOTE: Car Top Inspection operation automatically overrides Car Panel Inspection operation.
4. Run the car from the Car Top Inspection station, checking the up and down buttons and
the stop switch.
5. While running the car, check clearances and door locks. When all doors are locked,
remove any jumpers from door lock terminals.
6. Verify directional limit switch and final limit switch operation and position according to
page MRW1 or MRW2 of the job prints. The distance between the two switches should
ideally be greater than the distance required to stop the car after the direction command
is removed when the car is on Inspection operation.
7. Verify that the brake has sufficient tension to hold the car under all conditions likely to
be encountered during the installation phase.
Running on Machine Room Inspection