Drive - General Tab - MCi iControl User Manual

For ac elevators
Table of Contents

Advertisement

iView - Controller View

Drive - General Tab

Options
General drive setup:
• Drive type: Select the drive used in this controller.
• Drive interface: Select Analog or Serial.
• Motor blower hold delay: The motor blower is relay driven and shuts down when the
motor stops. This timer allows you to delay blower shutdown so that the motor may
receive additional cooling or so that the blower is not constantly power-cycled when the
motor is stopping for only a brief period.
Pre-Start Sequence
machine may be energized and/or the brake lifted prior to the default "After doors are locked"
state. Warning! Do not use Pre-Start Sequence options until drive control parame-
ters have been adjusted for no rollback and good control at zero speed.
• Allow machine to be energized: Defines the state of the doors required before the machine
is allowed to be energized:
• After doors are locked: Doors must be locked before the machine may be energized
(the motor is energized and brake is fully picked). Any soft lift brake adjustment is
applied.
• After door position monitor is activated: The door position monitor or doors locked
sensors must be activated before the machine may be energized (the motor is ener-
gized and brake is fully picked). If this option is selected, but the job doesn't have a
door position monitor, the machine is energized when the doors are locked. Any soft
lift brake adjustment is applied.
• While door are closing: Doors must be closing, then the machine may be energized as
follows:
• with motor and fully picked brake: The motor is energized and the brake is fully
picked. Any soft lift brake adjustment is applied.
• with motor and partially picked brake: The motor is energized and brake is partially
picked. The Speed pick delay 1 must expire and the doors must be locked before the
brake is fully picked. After the brake is fully picked, Speed pick delay 2 must expire
before the elevator is allowed to move. No soft lift brake adjustment is applied.
• with motor only: The motor is energized after the prescribed delay from doors clos-
ing. After the doors lock, the brake is fully picked, and Speed pick delay 1 must
expire before the elevator is allowed to move. Any soft pick brake adjustment is
applied.
• Pre-Start Sequence Delay: After the doors have begun to close, wait the specified time
before energizing the machine as defined as defined in "While doors are closing".
Note
Regardless of the selection above, the elevator is not allowed to move away from the landing
until the doors are locked and the Speed pick delay 1 timer has elapsed.
9-88 Manual # 42-02-2222