Fire Code - Recall - General Tab

This tab allows you to set various fire code recall parameters.
• Latch primary fire recall switch:
• Never: The recall condition will clear automatically when the initiating condition
clears.
• Fire device OFF: In order to clear the recall condition, the primary fire recall switch
must be off.
• Primary bypass: In order to clear the recall condition, the primary fire recall switch
must be turned to the BYPASS position.
• Bypass and recall completed: In order to clear the recall condition, the car must be at
the fire floor with doors open and the primary fire recall switch must be turned to the
BYPASS position.
• Recall completed all cars: In order to clear the recall condition, the fire recall must be
completed for all elevators in the group.
• Primary bypass then OFF: In order to clear the recall condition, the primary fire switch
must be turned to the BYPASS position and then back to off.