Final Adjustment
7.
If the car corrects and stops properly, proceed to
section.

If the Car Does Not Stop and Correct Properly

• Check the iBox status display. Verify:
• ULM, DLM, and DZ signals are working properly
• Safety OK = ON - safety string is made up.
• Doors Locked= ON - all doors are locked.
• Inspection = OFF - not on Inspection operation.
• Fault = OFF - no faults are active.

Initiating a One Floor Run

Note
Because we have not yet learned Normal and Emergency Terminal Limit switches, stay away
from the terminals to avoid tripping faults. Remember that Fault Bypasses are on a 15-minute
limit. If you need more time, set Fault Bypass quickly to OFF, then back to ON (within two sec-
onds).
The car should now be at a floor. Avoid running the car close to a terminal landing. To initiate a
one-floor run:
1. Register a car call one floor above or below the current
car position:
• Click the Car Call Registration button
• Select Car Calls, then Front or Rear panel.
• Click a floor selection button.

If Initiation is not Successful

If the car does not move, check the iBox status display. Verify:
• Safety OK = ON - safety string is made up.
• Doors Locked = ON - all doors are locked.
• Inspection = OFF - the car is not on Inspection operation.
• Faults = OFF - there are no active faults.
4-4 Manual # 42-02-2222
Initiating a One Floor Run
.