Table 6.3 iControl Messages
Excessive Restarts Warning
Description: The elevator has attempted to start movement from the same floor successively for an exces-
sive number of times. This fault is issued after ten attempts. The counter is reset if the car makes one suc-
cessful run.
Car Reaction: None.
Troubleshooting:
1. Check for mechanical or other failure preventing car from moving away from floor the floor.
Exercise Operation Activated, EXERCISE OPERATION
Description: The car has been idle for a predetermined user-defined time and is now performing a user-
defined number of Exercise operation runs.
Car Reaction: The car lowers to the bottom landing, then proceeds to the top landing and back down to the
bottom landing without cycling the doors. Moving the car to the top landing and then back down to the bot-
tom landing is considered one exercise run. The user defines the number of exercise runs.
Exercise Operation Deactivated
Description: The car has completed all of the exercise runs or Exercise operation has been terminated due to
change in mode of operation or calls being entered into the system.
Fault Bypass Switch On, FAULT BYPASS SW ON
Description: The iBox Fault Bypass switch is in the ON position.
Car Reaction: None.
Fault Bypass Switch Timed Out, FLT BYP SW TIMED OUT
Description: Indicates that a fault bypass has timed out. (Bypasses are allowed for 15 minutes with the iBox
Fault/Function Bypass switch in the ON position.)
Car Reaction: Emergency stop: Motor contactor and brake contactor immediately dropped.
Troubleshooting:
1. To clear this fault, place the Fault/Function Bypass switch to the OFF position.
F DPM OPEN-GS CLOSED. See Front DPM Open - GS Closed.
F DR CLS FLT REC FAIL. See Front Door Close Fault Recovery Failure
Field Module Over Temperature Fault, FIELD MODULE OVR TEMP
Description: The temperature of the Motor Field module heat sink is excessive (DC only).
Car Reaction: Stop at the next floor. Restart not permitted.
Troubleshooting:
1. Check machine room ambient temperature (should not exceed 104 degrees F or 40 degrees C).
2. Verify that air enters through the bottom of the power box and is only expelled via the fan at the top of
the power box.
3. Check for insufficient air circulation through the power box.
4. Check the running temperature inside the power box (should not exceed 105 degrees F).
5. Check for faulty field module.
6. Check for faulty iBox.
7. Check for faulty connection between motor field module and iBox.
Fire Service In-car Activated, Fire Service In-car, Fire Svc In-car
Description: In-car firefighters service has been activated via the in-car fire service key-switch.
Car Reaction: Car and Door operation is in accordance to the user-defined fire code. (iView/Car Operation/
Fire Service.)
Troubleshooting:
1. Related inputs:
FireIIOn: Normally low
FireIIOff: Normally high
FireIIHold: Normally low
iControl Messages
iControl Messages
6-35