MCi iControl User Manual page 500

For ac elevators
Table of Contents

Advertisement

iView - Controller View
• Latch secondary fire recall switch:
• Never: The recall condition will clear automatically when the initiating condition
clears.
• Fire device OFF: In order to clear the recall condition, the secondary fire recall switch
must be off.
• Primary bypass: In order to clear the recall condition, the primary fire recall switch
must be turned to the BYPASS position.
• Bypass and recall completed: In order to clear the recall condition, the car must be at
the fire floor with doors open and the primary fire recall switch must be turned to the
BYPASS position.
• Recall completed all cars: In order to clear the recall condition, the fire recall must be
completed for all elevators in the group.
• Primary bypass then OFF: In order to clear the recall condition, the primary fire recall
switch must be turned to the BYPASS position and then back to off.
• Latch first smoke detector zone:
• Never: The recall condition will clear automatically when the initiating condition
clears. When this option is set, the main floor smoke sensor will override the upper
floor smoke sensors.
• Fire device OFF: In order to clear the recall condition, the secondary fire recall switch
must be off.
• Primary bypass: In order to clear the recall condition, the primary fire recall switch
must be turned to the BYPASS position.
• Bypass and recall completed: In order to clear the recall condition, the car must be at
the fire floor with doors open and the primary fire recall switch must be turned to the
BYPASS position.
• Recall completed all cars: In order to clear the recall condition, the fire recall must be
completed for all elevators in the group.
• Primary bypass then OFF: In order to clear the recall condition, the primary fire recall
switch must be turned to the BYPASS position and then back to off.
• Fire Phase 1 nudging:
• No nudging: During Fire Phase I, nudging will be inhibited.
• Nudge if no reopen devices: During Fire Phase I, the doors will nudge close if there are
no operative reopening devices.
• Disable DOB and nudge during Fire Phase I:
• Not at all: The Door Open button will remain active.
• Immediately: The Door Open button will immediately become inactive when Fire
Phase I is initiated and the doors will nudge close if the Door Open Button is pressed as
the doors are closing.
• After delay: The Door Open Button will become inactive after the set delay when Fire
Phase I has been initiated and the doors will nudge close if the Door Open Button is
pressed as the doors are closing.
9-48 Manual # 42-02-2222