Calibration

Calibration allows iControl to learn the characteristics of the machine brake.
1. Verify that the iBox Safety OK LED is solidly on.
2. Set the iBox Learn switch to ON.
3. Place the iBox Inspection switch in the INSP position. Verify that the iBox displays
Machine Room Insp.
Note
If the iBox does not indicate that you are in Machine Room Inspection even though the Inspec-
tion switch is in the INSP position, another inspection mode (i.e., cartop inspection) is probably
active. Other inspection modes must be OFF before Machine Room Inspection can be activated.
COMPUTER
SAFETY A
SAFETY B
CARTOP
SYS COMM
4. Display the Brake > Control tab (Con-
figuration > Brake > Control tab).
5. Set Pick voltage and Hold voltage as
shown on your job prints.
6. For now, set Releveling voltage and
Weakening voltage to the same value
as Pick voltage. (This parameter can
be fine tuned during final adjust-
ment.)
UP
SAFETY OK
DRIVE ON
DOOR LOCKED
DOWN
INSPECTION
IN GROUP
RUN
RELEVEL
FAULT
Brake Calibration
CONTROLLER
STOP
INSPECTION
INSP
RUN
STOP
NORM
CAPTURE
UP
ON
OFF
ENABLE
TEST
ON
OFF
CAR DOOR
DOWN
BYPASS
BYPASS
OFF
FAULT/FUNCTION
BYPASS
ON
OFF
WRITE ENABLE
ON
OFF
LEARN
2
ON
OFF
HOISTWAY
DOOR BYPASS
BYPASS
OFF
2-51