Construction Mode

Electronic Motor Overload Protection Verification

Provided the car is running normally on Inspection operation and is drawing normal current,
perform the following test to verify the drive electronic motor overload protection is correctly
set to protect the motor from overload conditions:
1. Verify LF.08 (Electronic Motor Protection) is set to ON.
2. Note (write down) the value of LF.09 (Electronic motor protection current). This value
must be equal to LF.12.
3. Lower the value of LF.09 to 20% of the noted setting (LF.09 x 0.20).
4. Run the car on Inspection. After one minute the drive should trip an E.0H2 fault and
shut down the car.
5. After five seconds, the fault will automatically clear and the car will be ready to run on
Inspection again.
6. Set the value of LF.09 back to the noted setting (Motor FLA or LF.12).
2-60 Manual # 42-02-2222