Final Calibration with iControl

1. Connect the multi meter to test points TP_LW and GND on the ICE-CTP board inside
the iLink Cartop Box. Adjust trimpot LW ADJ until the multi meter reads the same as
the value noted in step 8.
Figure 6. ICE-CTP Cartop Processor Board
2. To view the voltage values from the load weigher using the iView Virtual Oscilloscope:
• Using iView, connect to the controller
• Display the Virtual Oscilloscope (View > Virtual Oscilloscope)
• Select Load Weigher (Raw) for Test point 1
• Observe the Load Weigher voltage values on the digital display.
3. To verify the linearity of the load weigher, place weights in the car that represent the fol-
lowing and observe the voltage values:
• Empty car - about 0.0 volts
• 25% of overload weight - about 2.5 volts
• 50% of overload weight - about 5.0 volts
• 75% of overload - about 7.5 volts
• Full load weight - about 8 volts
• Overload weight - about 10 volts
EMCO Load Weigher Installation and Calibration
TP_LW test point
LW ADJ trim pot
GND test point
5-59
5