MCi iControl User Manual page 584

For ac elevators
Table of Contents

Advertisement

iView - Controller View
Pattern Profile parameters
• Initial jerk: The transition from zero speed to full acceleration. As Initial jerk is increased,
the profile transitions more quickly from starting acceleration to maximum acceleration.
• Acceleration: Determines the maximum acceleration for this profile.
• High roll jerk: Used when the car is not able to reach High speed. Determines how quickly
the profile transitions from maximum to zero acceleration and zero to maximum decelera-
tion.
• High speed: Determines the maximum speed for this profile. (For the Standard profile this
is usually contract speed.
• Low roll jerk: Used when the car is able to reach High speed. Determines how quickly the
profile transitions from maximum to zero acceleration and zero to maximum deceleration.
• Deceleration: Determines the maximum deceleration for this profile.
• Flare jerk: The transition from maximum deceleration to Approach deceleration. As Flare
jerk is increased, the profile transitions more quickly.
• Approach deceleration: Determines the deceleration rate for the transition from Flare jerk
to Approach Jerk.
• Approach jerk: The transition from approach Deceleration to leveling speed. As Approach
Jerk is increased, the profile transitions more quickly.
• Low speed: The Low speed parameter is used only in Inspection mode. It determines the
reduced speed to which the car will decelerate after encountering a DNT5 or UNT5 switch
when operating in Inspection mode. (For example, if Inspection - High speed were set to
50 feet per minute and Low speed to 20 feet per minute, the car would decelerate from 50
fpm to 20 fpm if a terminal switch was encountered during Inspection operation.) Active
only when the Reduced inspection speed option is enabled.
• Reduced inspection speed: Specifies that the car, when in Inspection mode, will decelerate
to the Low speed setting if a DNT5 or UNT5 switch is opened.
Pattern shape preset
profile parameters based on the high speed (contract speed) of the elevator and the selected
shape type.
1. Speed: Enter the high speed (con-
tract speed of the elevator).
2. Shape type: Select the desired
shape type.
• Slow: Slow floor to floor times
with gentle transitions.
• Moderate: Moderate floor to floor times with moderate transitions.
• Fast: Fast floor to floor times with aggressive transitions.
3. Click Configure. Preset values for the pattern profile parameters are entered.
9-132 Manual # 42-02-2222
Pattern shape preset can be used to enter preset values for the