MCi iControl User Manual page 501

For ac elevators
Table of Contents

Advertisement

• Fire bypasses independent service:
• No bypass: Fire recall will not bypass Independent Service.
• Bypass immediately: Fire recall will immediately bypass Independent Service.
• Bypass if running or after delay: Fire recall will bypass Independent Service after the
delay set here expires or immediately if the car is running.
• Fire bypasses attendant service:
• No bypass: Fire recall will not bypass Attendant Service.
• Bypass immediately: Fire recall will immediately bypass Attendant Service.
• Bypass if running or after delay: Fire recall will bypass Attendant Service after the
delay set here expires or immediately if the car is running.
• Fire Switch Settings:
• Require primary and secondary switch activation to override alternate floor recall:
Enable if both primary and secondary fire switches must be active to override alternate
floor recall.
• Primary fire recall switch overrides alternate fire recall: Enable if primary fire recall
switch will override alternate fire recall.
• Secondary fire recall switch overrides alternate fire recall: Enable if secondary fire
recall switch will override alternate fire recall.
• Bypass position of primary recall switch bypasses sensors: Primary recall switch
bypass position will bypass smoke sensors.
• Primary fire switch recall resets alternate fire recall: Once the Phase I switch is used to
recall the car to the main recall floor, the main recall floor becomes the recall level for
the remainder of fire service operation regardless of the subsequent position of the fire
switch or the status of the main floor fire sensor (complies with A17.1a-2005 or later
code).
• Main Floor Sensor Options:
• Primary switch on to reset alternate recall: Recall to the alternate fire floor can only be
reset by putting the primary recall switch in the ON position (with this option
enabled).
• Alternate recall bypasses main recall: When a main floor recall is in process and an
alternate floor recall is initiated, the main recall will be bypassed and the alternate
recall will proceed (with this option enabled).
• Miscellaneous:
• Fire 1 bypasses stop switch: Fire 1 will bypass the stop switch.
• Fire 1 disables safety edge: Fire 1 will disable the door safety edge.
• Disable door contact monitoring during fire recall: Door contact monitoring shall be
disabled during fire recall.
• Attendant operated fire warning buzzer: The fire warning buzzer will only be activated
when the car is being operated by an attendant (required for British Fire Code EN 81-
72).
Configuration - Car Operation
9
9-49