p0779[0...2]

CU analog outputs characteristic value x2 / CU AO char x2

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Dependency:
See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
p0780[0...2]

CU analog outputs characteristic value y2 / CU AO char y2

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-20.000 [V]
Description:
Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
p0782[0...2]

BI: CU analog outputs invert signal source / CU AO inv S_src

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source to invert the analog output signals.
Index:
[0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
20.000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9572
Factory setting:
100.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9572
Factory setting:
20.000 [V]
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: 9572
Factory setting:
0