p5350[0...n]

Mot_temp_mod 1/3 boost factor at standstill / Standst boost_fact

Access level: 2
Can be changed: T, U
Unit group: -
Min:
1.0000
Description:
Sets the boost factor for the copper losses at standstill for motor temperature models 1 and 3.
The entered factor is active for speed n = 0 [rpm].
This factor is linearly reduced down to 1 between speeds n = 0 ... 1 [rpm].
The following values are required to calculate the boost factor:
- stall current (I_0, p0318, catalog value)
- thermal stall current (I_th0, catalog value)
The boost factor is calculated as follows:
- p5350 = (I_0 / I_th0)^2
Dependency:
See also: p0612, p5390, p5391
See also: F07011, A07012, F07013, A07014
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
Temperature model 1 (I2t):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
- parameter p5350 is not active. Internally, a fixed boost factor of 1.333 is used as basis for the calculation.
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
- parameter p5350 becomes active as described above.
r5389.0...8

CO/BO: Mot_temp status word faults/alarms / Mot_temp ZSW F/A

Access level: 2
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for faults and alarms of the motor temperature monitoring.
Bit field:
Bit
00
01
02
04
05
08
Dependency:
See also: r0034, p0612, r0632
See also: F07011, A07012, A07910
662
Signal name
Motor temperature measurement fault active
Motor temperature model fault active
Encoder temperature measurement fault active
Motor temperature measurement alarm active
Motor temperature measurement alarm active
Current reduction active
Calculated: -
Scaling: -
Unit selection: -
Max:
2.0000
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 8017
Factory setting:
2.0000
Data type: Unsigned16
Dynamic index: -
Function diagram: 8016
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
SINAMICS G120XA converter