The application class Standard Drive Control reduces the number of characteristics and setting
options:
● A linear and a parabolic characteristic are available.
● Selecting a technological application defines the characteristics.
Table 6-62
Requirement
The required
torque is inde‐
pendent of the
speed
The required
torque increa‐
ses with the
speed
Parameters
Number
r0025
r0066
r0071
p0310[M]
p501
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Linear and parabolic characteristics
Application exam‐
Remark
ples
Eccentric-worm
-
pump, compressor
Centrifugal
Lower losses in the motor and con‐
pumps, radial
verter than with the linear charac‐
fans, axial fans
teristic.
Name
CO: Output voltage, smoothed
CO: Output frequency
Output voltage, maximum
Rated motor frequency
Technology application
Advanced commissioning
6.6 Motor control
Charac‐
Parameter
teristic
Linear
p0501 = 0
Parabol‐
p0501 = 1
ic
Factory setting
- Vrms
- Hz
- Vrms
0 Hz
0