5.5

Analog outputs

Analog output terminals
CO: rxxyy
1
Define the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0
AO 1
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Figure 5-3
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
p0776[0]
p0771[0]
p0776[1]
p0771[1]
Not available with CU240B-2 and CU240B-2 DP Control Units
Current output (factory setting)
Voltage output
Current output
Current output (factory setting)
Voltage output
Current output
Examples for scaling characteristics
Changing the function of the analog output
1. Define the analog output type using parameter
p0776 (e.g. voltage output -10 V ... 10 V or
current output 4 mA ... 20 mA).
2. Interconnect parameter p0771 with a
connector output of your choice (e.g. the
actual speed).
In the parameter list of the List Manual,
connector outputs are marked with "CO".
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
Adapt terminal strip
5.5 Analog outputs
p0776[0] =
0
1
2
p0776[1] =
0
1
2
97