Digital Inputs - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

6.2.2.1

Digital inputs

Function description
To change the function of a digital input, you must interconnect the status parameter of the
digital input with a binector input of your choice.
Binector inputs are designated in the parameter list with the prefix "BI:".
Example
To acknowledge converter fault messages using digital input DI 1, you must interconnect DI 1
with the command to acknowledge faults (p2103).
Set p2103 = 722.1.
Parameters
Parameter
r0721
r0722
r0723
p0724
p0810
p0840[C]
p0844[C]
p0848[C]
p0852[C]
p1020[C]
p1021[C]
p1022[C]
p1023[C]
p1035[C]
p1036[C]
p1055[C]
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Description
CU digital inputs, terminal actual value
CO/BO: CU digital inputs, status
CO/BO: CU digital inputs, status inverted
CU digital inputs debounce time
BI: Command data set selection CDS bit 0
BI: ON/OFF (OFF1)
BI: No coast down/coast down (OFF2) signal
source 1
BI: No quick stop/quick stop (OFF3) signal source
1
BI: Enable operation/inhibit operation
BI: Fixed speed setpoint selection, bit 0
BI: Fixed speed setpoint selection, bit 1
BI: Fixed speed setpoint selection, bit 2
BI: Fixed speed setpoint selection, bit 3
BI: Motorized potentiometer setpoint higher
BI: Motorized potentiometer setpoint lower
BI: Jogging bit 0
Advanced commissioning
6.2 Drive control
Factory setting
-
-
--
4 ms
0
Dependent on the converter
Dependent on the converter
1
Dependent on the converter
0
0
0
0
Dependent on the converter
Dependent on the converter
Dependent on the converter
131