Mot_Temp_Mod 1/3 Ambient Temperature / Mod 1/3 Amb_Temp - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

08
09
12
Dependency:
For synchronous motors and synchronous reluctance motors, when exiting commissioning, temperature model 1 is
automatically activated if a time constant has been entered in p0611.
See also: r0034, p0604, p0605, p0611, p0613, p0615, p0625, p0627, r0632, p5350, r5389, p5390, p5391
See also: F07011, A07012, F07013, A07014, A07910
NOTICE
For bit 00:
This bit is only automatically activated for permanent-magnet 1FT7 synchronous motors and synchronous reluctance
motors. For other permanent-magnet synchronous motors, the user himself must activate motor temperature model
1 (I2t).
It is only possible to activate this motor temperature model (I2t) for a time constant greater than zero (p0611 > 0).
Note
Mot_temp_mod: motor temperature model
For bit 00:
This bit is used to activate/deactivate the motor temperature model for permanent-magnet synchronous motors and
synchronous reluctance motors.
For bit 01 (see also bit 9):
This bit is used to activate/deactivate the motor temperature model for induction motors.
For bit 08:
This bit is used to extend the motor temperature model 1 (I2t).
The following applies for firmware version < 4.7 SP6 (only bit 0):
- this bit has no function. Temperature model 1 operates in the standard mode.
Overtemperature at rated load: p0605 - 40 °C
Alarm threshold: p0605
Fault threshold: p0615
The following applies from firmware version 4.7 SP6 (bits 0 and 8):
- temperature model 1 operates in the extended mode.
Overtemperature at rated load: p0627
Alarm threshold: p5390
Fault threshold: p5391
For bit 09:
This bit is used to extend the motor temperature model 2.
For firmware version < 4.7 following applies (only bit 1):
- this bit has no function. Temperature model 2 operates in the standard mode.
From firmware version 4.7 the following applies (bits 1 and 9):
- this bit should be set. Temperature model 2 then operates in the extended mode and the result of the model is more
precise.
For bit 12 (only effective if a temperature sensor has not been parameterized):
This bit is used to set the ambient temperature for the motor temperature model 1 (I2t).
The following applies for firmware version < 4.7 SP6 (only bit 0):
- this bit has no function. Temperature model 1 operates with an ambient temperature of 20 °C.
The following applies from firmware version 4.7 SP6 (bits 0 and 12):
- the ambient temperature can be adapted to the conditions using p0613.
p0613[0...n]

Mot_temp_mod 1/3 ambient temperature / Mod 1/3 amb_temp

Access level: 2
Can be changed: T, U
Unit group: 21_1
Min:
-40 [°C]
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Activate mot_temp_mod 1 (I2t) extensions
Activate mot_temp_mod 2 extensions
Mot_temp_mod 1 (I2t) ambient temperature can be adjusted Yes (via p0613)
Yes
Yes
Calculated: -
Scaling: -
Unit selection: p0505
Max:
100 [°C]
Parameters
7.3 Parameters
No
-
No
-
No (fixed 20 °C)
-
Data type: FloatingPoint32
Dynamic index: MDS, p0130
Function diagram: 8017
Factory setting:
20 [°C]
419