Cu Invert Digital Outputs / Cu Do Inv; Bo: Cu Analog Inputs Status Word / Cu Ai Status Word; Co: Cu Analog Inputs Input Voltage/Current Actual / Cu Ai U/I_Inp Act - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p0748

CU invert digital outputs / CU DO inv

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Setting to invert the signals at the digital outputs.
Bit field:
Bit
00
01
02
03
Note
DO: Digital Output
Relay output: NO = normally open, NC = normally closed
r0751.0...11

BO: CU analog inputs status word / CU AI status word

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and binector output for the status of the analog inputs.
Bit field:
Bit
00
01
02
03
08
09
10
11
Note
AI: Analog Input
r0752[0...3]

CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act

Access level: 2
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Displays the actual temperature in °C when set as temperature sensor and the voltage divider is switched in.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Signal name
DO 0 (NO: X134. 19 / NC: X134. 18)
DO 1 (NO: X134. 21)
DO 2 (NO: X134. 24)
DO 3 (NO: X134. 51)
Signal name
Analog input AI0 wire breakage
Analog input AI1 wire breakage
Analog input AI2 wire breakage
Analog input AI3 wire breakage
Analog input AI0 no wire breakage
Analog input AI1 no wire breakage
Analog input AI2 no wire breakage
Analog input AI3 no wire breakage
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Inverted
Inverted
Inverted
Inverted
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: p0514
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: Unsigned32
Dynamic index: -
Function diagram: 2201, 2242
Factory setting:
0000 bin
0 signal
FP
Not inverted
-
Not inverted
-
Not inverted
-
Not inverted
-
Data type: Unsigned16
Dynamic index: -
Function diagram: 2251, 2252
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
-
431