r0209[0...4]

Power unit maximum current / PU I_max

Access level: 3
Can be changed: -
Unit group: -
Min:
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 load duty cycle
[4] = S6 load duty cycle
Dependency:
See also: p0205
p0210

Drive unit line supply voltage / U_connect

Access level: 3
Can be changed: T
Unit group: -
Min:
1 [V]
Description:
Sets the drive unit supply voltage (rms value of the phase-to-phase line supply voltage).
Dependency:
Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller (r1242, r1282) are then directly determined using p0210.
NOTICE
If, in the switched-off state (pulse inhibit), the supply voltage is higher than the entered value, the Vdc controller may
be automatically deactivated in some cases to prevent the motor from accelerating the next time the system is
switched on. In this case, an appropriate alarm A07401 is output.
Note
Setting ranges for p0210 as a function of the rated power unit voltage:
U_rated = 400 V:
- p0210 = 380 ... 440 V
U_rated = 690 V:
- p0210 = 500 ... 690 V
p0230

Drive filter type motor side / Drv filt type mot

Access level: 1
Can be changed: C2(1, 2)
Unit group: -
Min:
0
Description:
Sets the type of the filter at the motor side.
Value:
0:
1:
2:
3:
4:
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
No filter
Motor reactor
dv/dt filter
Sine-wave filter Siemens
Sine-wave filter third-party
Calculated: -
Scaling: -
Unit selection: -
Max:
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
63000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max:
4
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 8750, 8850,
8950
Factory setting:
- [Arms]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
400 [V]
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
381