Siemens SINAMICS G120XA Operating Instructions Manual page 531

Table of Contents

Advertisement

Note
For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
The following applies for a synchronous reluctance motor:
The scaling allows the flux setpoint to be adapted when operating with load-dependent optimum flux characteristic or
with constant flux setpoint.
p1570[0...n]
CO: Flux setpoint / Flex setp
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T, U
Unit group: -
Min:
50.0 [%]
Description:
Sets the flux setpoint referred to rated motor flux.
The following applies for a synchronous reluctance motor:
Scaling the flux setpoint.
Dependency:
See also: p0500
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
For p1570 > 100%, the flux setpoint increases as a function of the load from 100% (no-load operation) to the setting
in p1570 (above rated motor torque), if p1580 > 0% has been set.
The following applies for a synchronous reluctance motor:
The scaling allows the flux setpoint to be adapted when operating with load-dependent optimum flux characteristic or
with constant flux setpoint.
p1574[0...n]
Voltage reserve dynamic / U_reserve dyn
Access level: 3
Can be changed: T, U
Unit group: 5_1
Min:
0.0 [Vrms]
Description:
Sets a dynamic voltage reserve.
Dependency:
See also: p0500
Note
In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due to
the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage reserve.
Increasing the reserve reduces the steady-state maximum output voltage (r0071).
p1574[0...n]
Voltage reserve dynamic / U_reserve dyn
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T, U
Unit group: 5_1
Min:
0.0 [Vrms]
Description:
Sets a dynamic voltage reserve.
Dependency:
See also: p0500
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated:
CALC_MOD_LIM_REF
Scaling: PERCENT
Unit selection: -
Max:
200.0 [%]
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
150.0 [Vrms]
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
150.0 [Vrms]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6722
Factory setting:
103.0 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6723, 6724
Factory setting:
10.0 [Vrms]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6723, 6724
Factory setting:
2.0 [Vrms]
529

Advertisement

Table of Contents
loading

Table of Contents