Procedure
1. Switch on the motor with a setpoint of a few revolutions per minute.
2. Check whether the motor rotates smoothly.
3. If the motor does not rotate smoothly, or even remains stationary, increase the voltage boost
p1310 until the motor runs smoothly.
4. Accelerate the motor with the maximum load.
5. Check that the motor follows the setpoint.
6. If necessary, increase the voltage boost p1311 until the motor accelerates without problem.
In applications with a high break loose torque, you must also increase parameter p1312 in order
to achieve a satisfactory motor response.
You have set the voltage boost.
Parameters
Number
r0071
p0310[M]
p0320[M]
p1310[D]
p1311[D]
p1312[D]
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Name
Output voltage, maximum
Rated motor frequency
Rated motor magnetizing current / short-circuit current
Starting current (voltage boost) permanent
Starting current (voltage boost) when accelerating
Starting current (voltage boost) when starting
Advanced commissioning
6.6 Motor control
Factory setting
Vrms
0 Hz
0 Arms
50%
0%
0%
287