r1078

CO: Total setpoint effective / Total setpoint eff

Access level: 3
Can be changed: -
Unit group: 3_1
Min:
- [rpm]
Description:
Displays the total effective setpoint.
The value indicates the sum of the effective main setpoint and supplementary setpoint.
Note
If the fixed speed setpoint is the source for the speed setpoint, then when the extended service mode is activated
(r3889.0 = 1) fixed speed setpoint 15 is displayed.
p1080[0...n]

Minimum speed / n_min

Access level: 1
Can be changed: C2(1), T
Unit group: 3_1
Min:
0.000 [rpm]
Description:
Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency:
See also: p1106
WARNING
The minimum speed is preassigned to 20% of the rated motor speed.
After all of the enable signal have been switched on, with the appropriate direction specified, the motor accelerates to
this minimum speed.
NOTICE
The effective minimum speed is formed from p1080 and p1106.
Note
The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
p1081

Maximum speed scaling / n_max scal

Access level: 2
Can be changed: T, U
Unit group: -
Min:
100.00 [%]
Description:
Sets the scaling for the maximum speed (p1082).
For a higher-level speed control, this scaling allows the maximum speed to be briefly exceeded.
Dependency:
See also: p1082
NOTICE
Continuous operation above a scaling of 100 % is not permitted.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
- [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max:
19500.000 [rpm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
105.00 [%]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 3030
Factory setting:
- [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3050, 8022
Factory setting:
0.000 [rpm]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 3050, 3095
Factory setting:
100.00 [%]