Co/Bo: Control Word 1 / Stw 1; Co/Bo: Supplementary Control Word / Suppl Stw - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

r0054.0...15

CO/BO: Control word 1 / STW 1

Access level: 2
Can be changed: -
Unit group: -
Min:
-
Description:
Displays control word 1.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
13
14
15
Note
The following control bits are displayed in r0054:
Bit 00: r0898 Bit 0
Bit 01: r0898 Bit 1
Bit 02: r0898 Bit 2
Bit 03: r0898 Bit 3
Bit 04: r0898 Bit 4
Bit 05: r0898 Bit 5
Bit 06: r0898 Bit 6
Bit 07: r2138 Bit 7
Bit 08: r0898 Bit 8
Bit 09: r0898 Bit 9
Bit 10: r0898 Bit 10
Bit 11: r1198 Bit 11
Bit 13: r1198 Bit 13
Bit 14: r1198 Bit 14
Bit 15: r0836 Bit 0
r0055.0...15

CO/BO: Supplementary control word / Suppl STW

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for supplementary control word.
Bit field:
Bit
00
01
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Signal name
ON/OFF1
OC / OFF2
OC / OFF3
Enable operation
Enable ramp-function generator
Continue ramp-function generator
Enable speed setpoint
Acknowledge fault
Jog bit 0
Jog bit 1
Master control by PLC
Direction reversal (setpoint)
Motorized potentiometer raise
Motorized potentiometer lower
CDS bit 0
Signal name
Fixed setpoint bit 0
Fixed setpoint bit 1
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Parameters
7.3 Parameters
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
Yes
-
Yes
-
No
-
No
-
No
-
No
-
No
-
No
3030
No
3030
No
-
No
-
No
-
No
-
No
-
Data type: Unsigned16
Dynamic index: -
Function diagram: 2513
Factory setting:
-
0 signal
FP
No
-
No
-
367

Advertisement

Table of Contents
loading

Table of Contents