p0205

Power unit application / PU application

Access level: 1
Can be changed: C2(1, 2)
Unit group: -
Min:
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
1:
6:
7:
Dependency:
See also: r3996
NOTICE
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no influence
when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
p0205
Power unit application / PU application
CUG120XA_USS
Access level: 1
(PM330)
Can be changed: C2(1, 2)
Unit group: -
Min:
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
1:
Dependency:
See also: r3996
NOTICE
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no influence
when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
r0206[0...4]

Rated power unit power / PU P_rated

Access level: 2
Can be changed: -
Unit group: 14_6
Min:
- [kW]
Description:
Displays the rated power unit power for various load duty cycles.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Load duty cycle with high overload for vector drives
Load duty cycle with low overload for vector drives
S1 duty cycle (for internal use)
S6 duty cycle (for internal use)
Load duty cycle with high overload for vector drives
Load duty cycle with low overload for vector drives
Calculated: -
Scaling: -
Unit selection: -
Max:
7
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: p0100
Max:
- [kW]
Parameters
7.3 Parameters
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
1
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [kW]
379