Hysteresis Speed 3 / N_Hysteresis 3; Ci: Speed Setpoint For Messages/Signals / N_Set For Msg - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
Description:
Sets the configuration for messages and monitoring functions.
Bit field:
Bit
00
01
03
05
Dependency:
See also: r2197
See also: A07903
Note
For bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
For bit 01:
When the bit is set, the load monitoring is only executed in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
For bit 03:
When the bit is set, r2197.1 and r2197.2 are determined using separate hysteresis functions.
For bit 05:
When this bit is set, a change to open-loop speed controlled operation is only possible when the motor is stationary.
p2150[0...n]

Hysteresis speed 3 / n_hysteresis 3

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency:
See also: p2161, r2197, r2199
p2151[0...n]

CI: Speed setpoint for messages/signals / n_set for msg

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency:
See also: r2197, r2198, r2199
590
Signal name
Enable alarm A07903
Load monitoring only in the 1st quadrant
n_act > p2155 own hysteresis
Stall monitoring for encoderless speed control
1 signal
Yes
Yes
Yes
Yes
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
300.00 [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
0 signal
FP
No
8011
No
8013
No
8010
No
-
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8010, 8011,
8022
Factory setting:
2.00 [rpm]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 8011
Factory setting:
1170[0]
SINAMICS G120XA converter