6.4.2.3
Enable direction of rotation
Function description
In the factory setting of the converter, the negative direction of rotation of the motor is inhibited.
Set parameter p1110 = 0 to permanently enable the negative direction of rotation.
Set parameter p1111 = 1 to permanently inhibit the positive direction of rotation.
Parameters
Table 6-48
Number
p1110
p1111
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Application examples for inhibiting and enabling the direction of rotation
Name
BI: Inhibit negative direction
BI: Inhibit positive direction
Advanced commissioning
6.4 Setpoints and setpoint processing
Factory setting
1
0
237