Advanced commissioning

6.8 Drive availability

6.8
Drive availability
6.8.1
Flying restart – switching on while the motor is running
If you switch on the motor while it is still rotating, without the "Flying restart" function, there is
a high probability that a fault will occur as a result of overcurrent (F30001 or F07801). Examples
of applications involving an unintentionally rotating motor directly before switching on:
● The motor rotates after a brief line interruption.
● A flow of air turns the fan impeller.
● A load with a high moment of inertia drives the motor.
Principle of operation
The "Flying restart" function comprises the following steps:
1. After the on command, the converter impresses the search current in the motor and
increases the output frequency.
2. When the output frequency reaches the actual motor speed, the converter waits for the
motor excitation build up time.
3. The converter accelerates the motor to the actual speed setpoint.
Figure 6-74
Parameters
Table 6-71
Number
p1200[D]
No "Flying restart" function for group drives
It is not permissible that you enable the "Flying restart" function if the converter is
simultaneously driving several motors.
318

Principle of operation of the "flying restart" function

Setting "flying restart" function

Name
Flying restart operating mode
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Factory setting
0