Cavitation Protection - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

6.3.5

Cavitation protection

Overview
Cavitation problem can damage the impeller of the pumps, reduce the output water flow and
cause unexpected noise. The cavitation protection will generate a fault/warning when
cavitation conditions are deemed to be present. If the converter gets no feedback from the
pump transducer, it will trip to prevent cavitation damage. This function saves the maintenance
efforts and extends the lifetime expectancy of the system.
Function description
Parameters
Number
p29625
p29626
p29627
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Name
Cavitation protection enable
Cavitation protection threshold
Cavitation protection time
For more information about the parameters, see Chapter "Parameters (Page 349)".
Advanced commissioning
6.3 Pump control
Factory setting
0
40%
30 s