Load Monitoring Delay Time / Load Monit T_Del; Co/Bo: Status Word Monitoring 1 / Zsw Monitor 1 - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
Dependency:
The following applies: p2191< p2168 if p2168 <> 0
See also: p2181, p2182, p2184, p2193
See also: A07892, F07895, A07926
Note
For the setting p2191 = 0, the monitoring for dry running operation or belt breakage is deactivated.
Pre-assignment: p2191 = 5 % of the rated motor torque (p0333).
p2192[0...n]

Load monitoring delay time / Load monit t_del

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2193[0...n]
Load monitoring configuration / Load monit config
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the load monitoring configuration.
Value:
0:
1:
2:
3:
4:
5:
Dependency:
See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925, F07936
Note
p2193 = 4, 5 can only be combined with p2181 = 7, 8.
r2197.0...13

CO/BO: Status word monitoring 1 / ZSW monitor 1

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the first status word of the monitoring functions.
Bit field:
Bit
00
01
02
03
04
05
06
600
Monitoring switched out
Monitoring torque and load drop
Monitoring speed and load drop
Monitoring load drop
Monitoring pump and load failure
Monitoring fan and load failure
Signal name
|n_act| <= n_min p1080
|n_act| <= speed threshold value 2 p2155
|n_act| > speed threshold value 2 p2155
n_act >= 0
|n_act| >= n_set
|n_act| <= n_standstill p1226
|n_act| > n_max
Calculated: -
Scaling: -
Unit selection: -
Max:
65.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
5
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8013
Factory setting:
10.00 [s]
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 8013
Factory setting:
1
Data type: Unsigned16
Dynamic index: -
Function diagram: 2534
Factory setting:
-
0 signal
FP
No
8022
No
8010
No
8010
No
8011
No
8022
No
8022
No
8010
SINAMICS G120XA converter