If the converter does not output alarm A07991, switch off the motor as described below, and
switch over the converter control from HAND to AUTO.
Switch on the motor to start the rotating measurement.
During motor data identification, "MOT-ID" flashes on the BOP‑2.
The motor data identification can take up to 2 minutes depending on the rated motor power.
Depending on the setting, after motor data identification has been completed, the converter
switches off the motor - or it accelerates it to the setpoint.
If required, switch off the motor.
Switch the converter control from HAND to AUTO.
You have completed the motor data identification.
Quick commissioning has been completed once the motor data identification has been
successfully completed.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
5.4 Quick commissioning using the BOP-2 operator panel
Commissioning
123