Starting Current (Voltage Boost) When Accelerating / I_Start Accel; Starting Current (Voltage Boost) When Starting / I_Start Start - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
Note
The starting current as a result of the voltage boost is only effective for U/f control (p1300).
The boost values are combined with one another if the permanent voltage boost (p1310) is used in conjunction with
other boost parameters (acceleration boost (p1311), voltage boost for starting (p1312)).
However, these parameters are assigned the following priorities: p1310 > p1311, p1312
For field orientation (p1302 bit 4 = 1, not PM230, PM250, PM260), then p1310 together with p1311 and p1302.5 are
mainly responsible for the quality of the drive response.
p1311[0...n]

Starting current (voltage boost) when accelerating / I_start accel

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.0 [%]
Description:
p1311 only results in a voltage boost when accelerating and generates a supplementary torque to accelerate the load.
The voltage boost becomes effective for a positive setpoint increase and disappears as soon as the setpoint has been
reached. The build-up and withdrawal of the voltage boost are smoothed.
The magnitude of the boost in Volt at a frequency of zero is defined as follows (not for field orientation):
Voltage boost [V] = 1.732 * p0305 (rated motor current [A]) x r0395 (stator/primary section resistance [ohm]) x p1311
(voltage boost when accelerating [%]) / 100 %
Dependency:
The current limit p0640 limits the boost.
For field orientation (p1302 bit 4 = 1, not PM230, PM250, PM260), p1311 is pre-assigned by the automatic calculation.
For vector control, the starting current is realized using p1611.
See also: p1300, p1310, p1312, r1315
NOTICE
The voltage boost results in a higher motor temperature increase.
Note
The voltage boost when accelerating can improve the response to small, positive setpoint changes.
Assigning priorities for the voltage boosts: refer to p1310
For field orientation (p1302 bit 4 = 1, not PM230, PM250, PM260), then p1311 together with p1310 and p1302.5 are
mainly responsible for the quality of the drive response.
p1312[0...n]

Starting current (voltage boost) when starting / I_start start

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.0 [%]
Description:
Setting for an additional voltage boost when powering-up, however, only for the first acceleration phase.
The voltage boost becomes effective for a positive setpoint increase and disappears as soon as the setpoint has been
reached. The build-up and withdrawal of the voltage boost are smoothed.
Dependency:
The current limit p0640 limits the boost.
See also: p1300, p1310, p1311, r1315
NOTICE
The voltage boost results in a higher motor temperature increase.
512
Calculated: -
Scaling: -
Unit selection: -
Max:
250.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
250.0 [%]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6300, 6301,
6851
Factory setting:
0.0 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6300, 6301,
6851
Factory setting:
0.0 [%]