Analog Outputs - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters, chassis and wall/panel mounted devices with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.2.2.4

Analog outputs

Overview
Defining the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0
AO 1
Characteristics
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Figure 6-5
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Current output (factory setting)
Voltage output
Current output
Current output (factory setting)
Voltage output
Current output
Examples for scaling characteristics
Advanced commissioning
Changing the function of an analog output:
1. Define the analog output type using
parameter p0776.
2. Interconnect parameter p0771 with a
connector output of your choice.
See also Section: Interconnecting signals in
the converter (Page 447).
Connector outputs are marked with "CO" in
the parameter list of the List Manual.
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
6.2 Inverter control
p0776[0] =
0
1
2
p0776[1] =
0
1
2
163