Debypass Delay Time / Debypass T_Del; Bypass Delay Time / Bypass T_Del; Bypass Speed Threshold / Bypass N_Thresh; Bi: Bypass Control Command / Bypass Command - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p1263

Debypass delay time / Debypass t_del

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
p1264

Bypass delay time / Bypass t_del

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the delay time for switching to line operation for a non-synchronized bypass.
Dependency:
The "Bypass" function is only available for induction motors.
p1265

Bypass speed threshold / Bypass n_thresh

Access level: 2
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the speed threshold to activate the bypass.
Dependency:
The "Bypass" function is only available for induction motors.
If the drive setpoint speed is entered via a motorized potentiometer, then the configuration bit p1030.4 should be set
in order to ensure the bypass via speed threshold function.
Note
When selecting p1260 = 3 and p1267.1 = 1, the bypass is automatically activated when this speed is reached.
The bypass speed threshold is only effective for positive directions of rotation. If the drive connected to the line supply
requires negative speeds, then this can be achieved using p1820 (direction of rotation reversal).
p1266

BI: Bypass control command / Bypass command

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the control command to the bypass.
Dependency:
The "Bypass" function is only available for induction motors.
p1267
Bypass changeover source configuration / Chngov_src config
Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the cause that should initiate the bypass.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
300.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
300.000 [s]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1480.00 [rpm]
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned8
Dynamic index: -
Function diagram: -
Factory setting:
0000 bin
503

Advertisement

Table of Contents
loading

Table of Contents