Ci: Free Tec_Ctrl 2 Actual Value Signal Source / Ftec2 Act V S_S; Free Tec_Ctrl 2 Actual Value Smoothing Time Constant; Free Tec_Ctrl 2 Actual Value Upper Limit / Ftec2 Act V Up Lim; Free Tec_Ctrl 2 Actual Value Lower Limit / Ftec2 Act V Lo Lim - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
1:
CAUTION
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note
The correct setting can be determined as follows:
- inhibit free technology controller (p11200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the free technology controller).
- if the actual value increases with increasing motor speed, then deactivate inversion.
- if the actual value decreases with increasing motor speed, then activate inversion.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
p11264

CI: Free tec_ctrl 2 actual value signal source / Ftec2 act v s_s

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the actual value of the free technology controller 2.
p11265
Free tec_ctrl 2 actual value smoothing time constant / Ftec2 act v T
Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.00 [s]
Description:
Sets the smoothing time constant (PT1) for the actual value of the free technology controller 2.
p11267

Free tec_ctrl 2 actual value upper limit / Ftec2 act v up lim

Access level: 3
Can be changed: T, U
Unit group: 9_4
Min:
-200.00 [%]
Description:
Sets the upper limit for the actual value signal of the free technology controller 2.
Dependency:
See also: p11264
p11268

Free tec_ctrl 2 actual value lower limit / Ftec2 act v lo lim

Access level: 3
Can be changed: T, U
Unit group: 9_4
Min:
-200.00 [%]
Description:
Sets the lower limit for the actual value signal of the free technology controller 2.
Dependency:
See also: p11264
702
Inversion
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
60.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p11226
Max:
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p11226
Max:
200.00 [%]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
0.00 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
100.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030