Flux Control Configuration / Flux Ctrl Config - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
Note
For bit 16:
When the bit is set, the integral component of the speed controller is only held if it reaches the torque limit.
For bit 19, 20:
When this bit is set, speed overshoots when accelerating along the torque limit and for load surges are reduced.
For bit 20:
The acceleration model for the speed setpoint is only active if p1496 is not zero.
For bit 25:
When the bit is set, for high dynamic starting in the I/f mode, the acceleration precontrol torque smoothing only has a
short minimum time (4 ms).
p1400[0...n]
Speed control configuration / n_ctrl config
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the configuration for the closed-loop speed control.
Bit field:
Bit
00
05
15
16
18
19
20
21
22
25
Note
For bit 16:
When the bit is set, the integral component of the speed controller is only held if it reaches the torque limit.
For bit 19, 20:
When this bit is set, speed overshoots when accelerating along the torque limit and for load surges are reduced.
For bit 20:
The acceleration model for the speed setpoint is only active if p1496 is not zero.
For bit 25:
When the bit is set, for high dynamic starting in the I/f mode, the acceleration precontrol torque smoothing only has a
short minimum time (4 ms).
p1401[0...n]

Flux control configuration / Flux ctrl config

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the configuration for flux setpoint control
Bit field:
Bit
01
518
Signal name
Automatic Kp/Tn adaptation active
Kp/Tn adaptation active
Sensorless vector control speed precontrol
I component for limiting
Reserved
Anti-windup for integral component
Acceleration model
Free Tn reduction active
Reserved
Acceleration torque instantaneous in the I/f mode
Signal name
Flux setpoint differentiation active
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Enable
-
Yes
ON
Yes
-
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Unsigned32
Dynamic index: DDS, p0180
Function diagram: 6490
Factory setting:
0000 0000 0011 1000 1000
0000 0010 0001 bin
0 signal
FP
No
6040
No
6040
No
6030
Hold
6030
-
-
No
6030
OFF
6031
No
6030
-
-
No
-
Data type: Unsigned16
Dynamic index: DDS, p0180
Function diagram: 6491
Factory setting:
0000 0000 0000 1110 bin
0 signal
FP
No