Advanced commissioning
6.8 Drive availability
Suppressing the automatic restart only functions for the setting p1210 = 6, 16 or 26.
Note
Motor starts in spite of an OFF command via the fieldbus
The converter responds with a fault if fieldbus communication is interrupted. For one of the
settings p1210 = 6, 16 or 26, the converter automatically acknowledges the fault and the motor
restarts, even if the higher-level control attempts to send an OFF command to the converter.
● In order to prevent the motor automatically starting when the fieldbus communication fails,
you must enter the fault number of the communication error in parameter p1206.
Parameter
Number
p1206
p1210
p1211
p1212
p1213[0]
p1213[1]
p29630
322
Name
Automatic restart faults not active
Automatic restart mode
Automatic restart, start attempts
Automatic restart, wait time start attempts
Automatic restart monitoring time
for restart
Reset automatic restart monitoring time for
start-up counter
Activate continuous operation
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Factory setting
0
0
3
1 s
60 s
0 s
0
SINAMICS G120XA converter