Off Delay N_Act = N_Set / T_Del_Off N_I=N_So; Switch-On Delay N_Act = N_Set / T_On N_Act=N_Set; Load Monitoring Stall Monitoring Torque Threshold / Stall_Mon M_Thresh - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Note
For p2165 = 0 or p2165 < p2182, the following applies:
There is no special stall monitoring for the pump/fan, but only the remaining load monitoring functions (e.g. leakage
monitoring for a pump) for the pump or fan are active.
p2166[0...n]

Off delay n_act = n_set / t_del_off n_i=n_so

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.0 [ms]
Description:
Sets the switch-off delay time for the "speed setpoint - actual value deviation in tolerance t_off" signal/message (BO:
r2197.7).
Dependency:
See also: p2163, p2164, r2197
p2167[0...n]

Switch-on delay n_act = n_set / t_on n_act=n_set

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.0 [ms]
Description:
Sets the switch-on delay for the "speed setpoint - actual value deviation in tolerance t_on" signal/message (BO:
r2199.4).
p2168[0...n]

Load monitoring stall monitoring torque threshold / Stall_mon M_thresh

Access level: 3
Can be changed: T, U
Unit group: 7_1
Min:
0.00 [Nm]
Description:
Sets the torque threshold of the stall monitoring of the pump or fan.
If, in the monitored speed range from p2182 to p2165, the torque exceeds this threshold, then this is evaluated as
either the motor having stalled or heavy-duty starting.
Dependency:
For pumps, the following applies (p2193 = 4):
- the leakage characteristic must lie below the torque threshold for the stall monitoring
- the torque threshold for dry running operation must lie below the torque threshold for stall monitoring
For fans, the following applies (p2193 = 5):
- the torque threshold for the stall monitoring must lie above the torque threshold to identify belt breakage (p2191).
See also: p2165, p2181, p2191, p2193
See also: A07891, F07894, A07926
Note
The following applies for p2168 = 0:
The special stall monitoring for pump/fan is deactivated.
Then, only the remaining load monitoring functions (e.g. the leakage monitoring for a pump) for pump or fan are
realized.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.0 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.0 [ms]
Calculated: -
Scaling: -
Unit selection: p0505
Max:
20000000.00 [Nm]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8011
Factory setting:
200.0 [ms]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8011
Factory setting:
200.0 [ms]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8013
Factory setting:
10000000.00 [Nm]
593