Technology Controller Tn Adaptation Lower Starting Point; Technology Controller Tn Adaptation Upper Starting Point; Co: Technology Controller Tn Adaptation Output / Tn Adapt Output; Techn. Controller Threshold Value F. I Comp. Hold For Skip Speed - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Note
Tn adaptation is activated with p2252.8 = 1.
p2320
Technology controller Tn adaptation lower starting point / Tn adapt lower pt
Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.00 [%]
Description:
Sets the lower activation point for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2319, p2321, r2322
CAUTION
The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note
Tn adaptation is activated with p2252.8 = 1.
p2321
Technology controller Tn adaptation upper starting point / Tn adapt upper pt
Access level: 2
Can be changed: T
Unit group: -
Min:
0.00 [%]
Description:
Sets the upper activation point for the adaptation of integral time Tn for the technology controller.
Dependency:
See also: p2317, p2318, p2319, p2320, r2322
CAUTION
The upper starting point must be set higher than the lower starting point (p2321 > p2320).
Note
Tn adaptation is activated with p2252.8 = 1.
r2322

CO: Technology controller Tn adaptation output / Tn adapt output

Access level: 2
Can be changed: -
Unit group: -
Min:
- [s]
Description:
Display and connector output for the output signal of the adaption of integral time Tn for the technology controller.
Dependency:
See also: p2252, p2317, p2318, p2319, p2320, p2321
Note
Tn adaptation is activated with p2252.8 = 1.
p2339
Techn. controller threshold value f. I comp. hold for skip speed / Tec_ctrl thr_skip
Access level: 3
Can be changed: T, U
Unit group: 9_1
Min:
0.00 [%]
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
400.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
400.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.00 [%]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
0.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
100.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
- [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
2.00 [%]